The ADCA P20DS is a series of direct acting, spring loaded, diaphragm
sensing balanced plug pressure reducing valves.
These regulators are particularly suitable for general purpose
applications where low flow and high temperatures are involved and
have been especially designed for use with steam.
Compact design.
Robust stainless steel diaphragm.
Non-rising adjustment knob.
Balanced valve plug.
Completely machined from solid bar stock material.
OPTIONS: |
Leakage line connection. Gauge connection on body. Different soft valves for liquids and gases. Top cap (adjustment screw with cover). Degreased for oxygen application. Connection for external sensing line. Panel mounting. |
USE: |
Steam, compressed air and other gases compatible with the construction. |
AVAILABLE MODELS: |
P20DS – stainless steel, diaphragm sensing. |
SIZES: |
1/4″ to 1/2″; DN 8 to DN 15. |
CONNECTIONS: |
Female threaded ISO 7 Rp, ISO 228 or NPT. Flanged EN 1092-1 PN 40. Flanged ASME B16.5 Class 150 or 300. |
INSTALLATION: |
Horizontal or vertical installation. |
LIMITING CONDITIONS
Valve model |
P20D |
|||
Body design conditions
|
Class 150
|
Class 300
|
PN 40
|
|
Maximum upstream pressure
|
14 bar
|
14 bar
|
14 bar
|
|
Maximum downstream pressure
|
8 bar |
8 bar |
8 bar |
|
Manimum downstream pressure |
0.2 bar |
0.2 bar |
0.2 bar |
|
Max. design temperature |
200 ºC |
200 ºC |
200 ºC |
|
Max. recommended reducing ratio |
10:1 |
10:1 |
10:1 |